Yes
ACI 318 imposes restrictions on special seismic systems in seismic categories C, D, E, and F. Thus, using ES600 shall be safe in seismic category A & B.
Elements that are controlled by flexure or tension stress such as. Foundation, Slabs, beam, and tension element (ties) will give the most savings.
Yes.
According to AC525 clause 1.21.1 “does not permit the use of intermediate high strength steel grade 90 (ES600) in the longitudinal bars of special moment frames, special structure walls boundary elements and coupling beams in seismic design category D, E & F” . However, according to ACI 318 -19 Footnote no. 4 table 20.2.2.4 (a) limits the fy of the longitudinal bars of intermediate moment frames to 550 Mpa 80 Ksi. It is good to mention that not all frame elements in a structure should be designed as moment intermediate frames unless they are designated structure elements and part of the lateral stability system of a moment frame system or dual system.
Yes, nothing in the code prohibits such use.
However, the execution team and building inspector need to ensure good QAQC practice.
Yes. According to ACI 318-19 table 20.2.2.4 (a) it allows using different rebar grades in the same elements such as boundary elements confinement and spandrel beams diagonal rebars to reduce the rebar congestion.
ES600 can be used in specific elements or specific floors. See answers to Q # 4 and 5
See ACI 318-19 Section 25.5.2.2: If bars of different size are lap spliced in tension, lst shall be the greater of ld of the larger bar and lst of the smaller bar.
No, it is around 20-30% higher. AC 525 clause 4.1.4 Recommendation should be followed.
550 Mpa limitation should be considered only for load combinations that are causing compression stress on columns which is the most common case. However, in cases that are column design is governed by tension stress 600 Mpa can be used.
Higher couplers are required and the AC133 quality control program should be followed in accordance with AC525 clause 5.2.
Dextra and Lenton have confirmed that their couplers commonly available in UAE can be used for ES600.
12 m
No special requirement for concrete. The only requirement for a minimum fc’ according to table 19.2.1.1 ACI 318 -19 of should be followed.
No Limitation actually it is recommended to use high-strength concrete with high-strength rebars Can we use ES600 for post-tension slab & prestressed?
Yes, nothing in the code prohibits the use of high strength rebars in post-tension slabs
Yes, However, specification is not within the scope of AC525. Will depend upon the bridge spec being used.
Yes, However, the current acceptance criteria from ICC (AC525) is for building application only. Piles are used to support buildings. So they are within the scope of the 2021 IBC and AC525.
Fatigue testing has been done and fatigue properties of ES600 are comparable with B500B. ie : No failure until 1 Million cycles.
Yes, Please see AC525 & ESR-4800
Below photographs clearly show the difference in marking between B500B and ES600.